Tests For: Sulfite in Boiler Water
Tests Range: 0–500 mg/L
Reagent Chemistry Used: Bleaching of indicator
Method Detection Limit*: 3.9 mg/L
Limit of Quantification**: 12.5 mg/L
Oxygen is a major cause of corrosion in boilers and steam raising plant. Sodium sulfite and catalysed sulfite formulations are extensively used as oxygen scavengers in boiler water treatment.
The Palintest Sulfite test provides a simple means of measuring sulfite levels for the control of such treatments in boiler plant. The test covers the range 0–500 mg/L Na2SO3.
The Palintest Sulfite test is based on a colorimetric procedure involving the reduction of an indicator dye. Sulfites react with the indicator dye under buffered conditions to destroy the original purple colouration. With increasing sulfite concentrations, a range of colours from purple to colourless is produced.
An advantage of the sulfite test method is that it does not respond to other reducing species as do traditional iodometric methods.
The degree of colour loss observed in the test is proportional to the sulfite concentration and is measured using a Palintest Photometer.
The Palintest Sulfite test is based on a colorimetric procedure involving the reduction of an indicator dye. Sulfites react with the indicator dye under buffered conditions to destroy the original purple colouration. With increasing sulfite concentrations, a range of colours from purple to colourless is produced.
An advantage of the sulfite test method is that it does not respond to other reducing species as do traditional iodometric methods.
The degree of colour loss observed in the test is proportional to the sulfite concentration and is measured using a Palintest Photometer.